Summary
Successful exploitation of this vulnerability could allow any authenticated user to create projects.
The following versions of Inductive Automation Ignition are affected:
- Ignition <=8.1.53 (CVE-2026-77393)
| CVSS | Vendor | Equipment | Vulnerabilities |
|---|---|---|---|
| v3 8.8 | Inductive Automation | Inductive Automation Ignition | Incorrect Default Permissions |
Background
- Critical Infrastructure Sectors: Critical Manufacturing, Energy, Information Technology
- Countries/Areas Deployed: Worldwide
- Company Headquarters Location: United States
Vulnerabilities
CVE-2026-77393
In Ignition 8.1.53 and earlier, the Gateway "Create Project Role(s)" setting shipped blank, which permitted any authenticated user to create projects (if they can execute gateway scripts). Ignition 8.1.54 restricts project creation to Designer sessions and no longer relies on this setting. The 8.3 series is not affected.
Affected Products
Inductive Automation Ignition
Inductive Automation
Inductive Automation Ignition: <=8.1.53
known_affected
Remediations
Mitigation
Inductive Automation has determined that this issue is a default-value configuration, not a flaw in the access control itself. The security control enforces exactly what the "Create Project Role(s)" setting specifies; because the setting shipped blank, no role was required to create a project. Populating the setting fully closes the vulnerability.
Mitigation
Inductive Automation recommends users upgrade to 8.1.54 or later (or the latest 8.3 version), which restricts project creation to Designer sessions and no longer relies on this setting. Users who must remain on an earlier 8.1 version can fully remediate the issue by setting "Create Project Role(s)" to match their Designer Role. Once the setting is populated, only users holding that role can create projects. See Gateway General Security Settings.
https://docs.inductiveautomation.com/docs/8.1/platform/security/gateway-general-security-settings#gateway-security-settings-table
Mitigation
For more information, see the publication at the Inductive Automation Trust Center.
https://security.inductiveautomation.com/?tcuUid=34477620-731d-4b70-b22b-9450f9a659a3
Relevant CWE: CWE-276 Incorrect Default Permissions
Metrics
| CVSS Version | Base Score | Base Severity | Vector String |
|---|---|---|---|
| 3.1 | 8.8 | HIGH | CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H |
| 4.0 | 8.7 | HIGH | CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N |
Acknowledgments
- Christopher Lusk of North Echo Security Research reported this vulnerability to Inductive Automation.
- Elhussain Fathy (0xSphinx) independently reported this vulnerability and confirmed the fix.
- Inductive Automation reported this vulnerability to CISA.
Legal Notice and Terms of Use
This product is provided subject to this Notification (https://www.cisa.gov/notification and this Privacy & Use policy (https://www.cisa.gov/privacy-policy
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as virtual private networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
CISA also recommends users take the following measures to protect themselves from social engineering attacks: Do not click web links or open attachments in unsolicited email messages. Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams. Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.
No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.
Revision History
- Initial Release Date: 2026-09-03
| Date | Revision | Summary |
|---|---|---|
| 2026-09-03 | 1 | Initial Republication of Inductive Automation Trust Center update. |
Legal Notice and Terms of Use
This product is provided subject to this Notification and this Privacy & Use policy.
Vendor
- Inductive Automation
